The debugging content of the smoke exhaust system of the water curtain fan includes: ① Adjusting the action of the smoke exhaust port. Each smoke exhaust outlet should be opened and closed according to the design requirements Measurement and adjustment of exhaust air volume.
The debugging content of the positive pressure air supply water curtain fan system includes: ① adjusting the action of the air supply outlet. Each air supply outlet should be opened and closed according to the design requirements Measurement and adjustment of air supply volume. ③ Measurement and adjustment of positive pressure. Adjust the overpressure exhaust equipment and system valves to ensure that the indoor positive pressure meets the relevant regulations of fire protection and design.
Review whether the debugging instruments and tools meet the debugging requirements. The instruments for water curtain fan commissioning shall be complete, and the performance shall meet the test requirements. The Debugger required for commissioning shall be made or purchased as required.
The debugged instruments and tools include: ① dry and wet bulb thermometers. ② Anemometer. ③ Micro differential pressure gauge. ④ Orifice plate flowmeter. ⑤ Rectifier grid. ⑥ Sound level meter.
Is the schedule of the water curtain fan in accordance with the requirements of the schedule and debugging procedures.